Sign In | Join Free | My rc363.com |
|
Place of Origin : Changzhou City China
Brand Name : FangSheng
Certification : ISO9001
MOQ : 500 Square Meter/Square Meters
Price : 1.00USD
Packaging Details : Wood pallet ,boxes
Delivery Time : Prompt
Payment Terms : T/T or L/C
Supply Ability : 2000㎡/Day
Type of Flooring: anti-static vinyl floor tile
Dimension: |
600 mm X 600 mm X 4.5 mm |
(special run for 24” x 24”) |
Total thickness: 4.5 mm
Total weight per sq. meter: 8.0 kg
Tests:
Surface resistively: 106 ~ 109 ohms (ASTM D257)
Electrostatic propensity: less than 0.6 kV (AATCC 134-01)
Fire index: Class 1 (NFPA 253 / ASTM E-648)
Dimension stability: < 0.15% (Aachen Dimensional Stability Evaluation)
Taber wear test: less than 0.007 mm loss (500 cycles - ASTM D4060)
Chemical resistance: no change (24 hours ratings ASTM F925-02)
Static Load: < 2.0% compression (ASTM F970-00 static load limit 125 LB)
Color: 8 standard colors
Special run color: minimum 500 sq. meters
Packing: 8 pieces per box
Color variation: Colors may vary due to different production lot.
Maintenance:
Quality assurance
Warranty: limited 5 years warranty.
Product improvement: In order to pursue product improvement, the manufacturer reserves the right to change specifications without prior notice
(1)the requirements of foundation
1.The ground should be waterstone ground, caramic tile groud, wooden ground or cement ground.
2.The ground should be smooth and level.Its unflatness should be less than 0.2%.
3.The ground should have enough strength and no the phenomenon of sand comimg out and separation.
4.The ground should be dry.It is necessary for a new ground to dry about 30days.
(2)Procedure of construction
Clean the ground→spread the earthing conductive net→lead out the earthing line→coat strong adhesive→coat conductive adhesive→lay floor→welding floor→cleaning→inspect properties
(3)Maintenance of floor
1.It is not permitted that sharp and rough heavy matters scribe and drag on the surface of floor and that personnel who wear shoes with nails walk on the floor.The floor should be kept cleaning.
2.It is not permitted that the chairs which have black rubber cushion put on the floor in order to avoid black sulfied polluting its surface.
3.If there are oil or dirty on its surface, it may be cleaned with detergent.If there is scribed sign, if can be recovered through fine abrasive paper.
4.If there are heavy oil and dirty caused by install equipments.Our factory has special washer to clean them.
5.Our factory also has anti-static wax that can be used to maintain the floor.In general, it should be coated one time every six months.If the personnel walking on the floor are busy, it should it should be coated every three months.
![]() |
4.5 mm thickness Anti Static PVC Flooring 600 * 600 * 4.5mm Images |